Saturday, May 6, 2017

Komponen Elektrik

MCCB – Moulded Case Circuit Breaker
·        Protection against Overload (Thermal Tripping) and Short Circuit (Magnetic Tripping)
-        Thermal tripping (overload) normally can set at 50%, 75%, 100%
-        Magnetic tripping (short circuit) can set for Icu, Ics
·        Standard Rating: 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A, 320A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1600A
·        Pole: 1, 2, SPN, 3, 4, TPN
·        Category: A (no short circuit trip delay), B (in built time delay maybe adjustable): 125A to 1600A
·        Breaking Capacity: 
-        Icu: Ultimate short circuit capacity
-        Ics: Service short circuit breaking capacity
-        Icw: Short time withstand current (0.05 – 0.1 – 0.25 – 0.5 – 1s)
·        Energy liminating class: 1 (no limit), 2 (370 kA²s), 3 (110 kA²s)
·        Example write-up in the drawing:


MCB – Miniature Circuit Breaker
·        MCBs provide overcurrent and short-circuit protection only and are unable to detect residual current (earth leakage current) unless it is large enough to be classed as an overload or short circuit.
·        IEC 60898 (domestic/unsupervised) & IEC 609947-2 (industry/supervised)
·        Standard Rating: 0.5A, 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 90A, 100A, 125A
·        Breaking Capacity: 3 – 25kA
·        Pole: 1, 2, 3, 4
·        Magnetic Trip Type: B (socket), C (lighting, fan), D (Aircond, motor, sodium lighting)
·      Type B MCBs react quickly to overloads, and are built to trip when the current passing through them is between 3 and 4.5 times the normal full load current. They are suitable for protecting incandescent lighting and socket-outlet circuits in domestic and commercial environments, where there is little risk of current surges of a magnitude that could cause the MCB to trip.
·   Type C MCBs react more slowly, and are recommended for applications involving inductive loads with high inrush currents, such as fluorescent lighting installations. Type C MCBs are built to trip at between 5 and 10 times the normal full load current.
·   Type D MCBs are slower still, and are set to trip at between 10 and 20 times normal full load current. They are recommended only for circuits with very high inrush currents, such as those feeding transformers and welding machines.
Type K MCBs are designed to trip at between 8 and 12 times normal full load current, placing them between the traditional
Type C and Type D breakers. In most cases, they allow improved cable protection to be provided in circuits that include motors, capacitors and transformers, where it would previously have been necessary to use Type D devices. This enhanced protection is achieved without increasing the risk of nuisance tripping.
·        Energy liminating class: 1 (no limit), 2 (370 kA²s), 3 (110 kA²s)
·        Example write-up in the drawing:


RCD – Residual Current Device
·       Intended principally to minimise the risk of injury from electric shock, RCCBs provide protection against residual (earth leakage) currents only, and are not sensitive to overloads or short circuits. For this reason, they must never be used as the sole protection device for a circuit.
Circuits with RCCB protection must always include separate protection against overloads and short circuits. This is most often an MCB, but it could, for example, be a fuse.

·       Like MCBs, RCCBs are available in various different types that are designated by letters. This is a potential source of confusion so it’s worth remembering that a Type B MCB, for example, is not related to a Type B RCCB.
·       RCCB (Residual Current Circuit Breaker)
·        RCBO (Residual Current Breaker with Overcurrent)
·        Pole: 2, 4
·        Tripping current: 6mA, 10mA, 100mA, 300mA, 500mA
·        Standard Rating: 10A, 13A, 16A, 20A, 25A, 32A, 40A, 63A, 80A, 100A, 125A
·        Type: G, S (time tripping can be delay)
·        Class: AC, A (recommended), B (3ph inverter), F (1ph inveter)
·        Example Write-up in the drawing:

The earth fault protection system is designed as below:
·   Each incoming power for DB and SSB up to 100A is protected by RCCB (Residual Current Circuit Breaker).
·   Each incoming power for DB and SSB within 125A and 300A is protected by Earth Leakage Relay (ELR),
·  Each incoming power for DB and SSB above 400A and above is protected by Earth Fault (EF) Protection Relay.
·  As additional protection by client, all the outgoing circuit from the MSB and ESSB must be protected by the Earth Fault (EF) Protection Relay.
·   Refer to Energy Commission (ST), the sensitivity for RCD shall be as following:-
-       All installation (1 phase & 3 phase): 100mA (0.1A)
-       Final switch socket: 30mA (0.03A)
-       Wet area, i.e. toilet & wet kitchen: 10mA (0.01A)

Monday, May 1, 2017

Current Carrying Capacity for Cable

CURRENT CARRYING CAPACITY FOR CABLE

               Current carrying capacity is defined as the amperage a conductor can carry before melting either conductor or insulation. Heat, cause by an electrical current flowing through a conductor, will determine amount of current a cable can handle.  Cables may be seriously damaged, leading to early failure, or their service lives may be significantly reduced, if they are operated for any prolonged periods at temperature above those corresponding to the tabulated current-carrying capacities.

The tabulated current-carrying capacities are based upon an ambient air temperature 30o C. When the surrounding temperature is higher than 30°C, the conductor’s operating temperature will also increase and the current carrying capacity of the conductor will be reduced. For other values of ambient air temperature it is necessary to apply a correction factor (multiplier) to obtain the corresponding effective current-carrying capacity.

The following formula applies.
a)      It =                      In                                                           
                              Ca x Cg x Ci x Ct                              

Iz            the current-carrying capacity of a cable for continuous service, under the particular installation condition concerned
It            the value of current tabulated in this appendix for the type of cable and installation method concerned, for a single circuit in an ambient temperature 30˚C.
Ib            the design current of the circuit, i.e. the current intended to be carried by the circuit in normal service.
In            the nominal current or current setting of the device protecting the circuit against overcurrent
I2            the operating current (i.e. the fusing current or tripping current for the conventional operating time) of the device protecting the circuit against overload
C             a correction factor to be applied where the installation conditions differ from those for which values of current-carrying capacity are tabulated in this appendix. The various correction factors are identified as follows:-
               Ca          for ambient temperature
               Cg          for grouping
               Ci            for thermal insulation
               Ct           for operating temperature of conductor


Determination of the size of cable to be used

Example for EMSB to ESSB-LP

In = 600 A                          
Ca= 0.97 (refer to Table 4C1, IEEE), assuming ambient temperature of 35°C for thermosetting cable)
Cg=0.8 (refer to Table 4B2, IEEE) I, total 3 core cable touching Horizontal/Vertical)
Ci=1.0 (cable not run in enclosed thermal insulation material)
Ct=1.0 (1.45/2=0.725 for BS3036 semi-enclosed fuse)

It  =                 600            
                0.97 x 0.8 x 1 x 1
    = 773.20 A
Referring to Table 4E1A, IEEE for XLPE/PVC cable,  4/1C x 400mm2 cable on tray has a current carrying capacity of 849 A.

Example for ESSB-LP to SUBMAIN NO.5

In = 200 A                          
Ca= 0.97 (refer to Table 4C1, IEEE), assuming ambient temperature of 35°C for thermosetting cable)
Cg=0.8 (refer to Table 4B2, IEEE), total 3 core cable touching Horizontal/Vertical)
Ci=1.0 (cable not run in enclosed thermal insulation material)
Ct=1.0 (1.45/2=0.725 for BS3036 semi-enclosed fuse)

It  =                 200            
                0.97 x 0.8 x 1 x 1
    = 257.73 A

Referring to Table 4E1A, IEEE for XLPE/PVC cable,  4/1C x 95mm2 cable on tray has a current carrying capacity of 341 A.


Lighting Design

LIGHTING DESIGN

Room Index
               The absolute values of room dimensions are not important; it is the relationship between area, parameter and height of the source of light which matters. It is found convenient to describe room proportions in term of room index.

Room Index, k =               LW        
                                                   Hm (L + W)

Where,  L = Length
                W = Width
                Hm = height of luminaries above the working plane

Mounting Height (HM)
               Mounting height usually is the vertical distance between a luminaire and the working plane, but it is sometimes the distance between the luminaire and the floor.

Utilization Factor (UF)
               U.F is the local flux reaching the working plane (or some other specified surface) divided by the total lamp flux. The value of the ratio depends partly on the room size and reflectance.

Light Loss Factor (LLF)
               The ratio of the illuminance provide at some stated time to the initial illuminance i.e after 100 hours. LLF is the product of the lamp lumen maintenance factor (LLMF), the luminaire maintenance factor (LMF) and the room surface maintenance factor (LMF) and the room surface maintenance factor (SRSMF)

Lumens and lumen-hours
               It would strictly be better to say “lumen output” or “total luminous flux” since the lumen measure flow rather the cumulative quantity a lamp which fail after 1100 hours delivering an average flux of 700 lumens has given a light output of 770,000 lumen-hours, but rarely concerned with this and in ordinary way we speak of a “light output” of 700 lumens.

Illuminance
               The illuminance of a surface is a measure of the concentration of light falling on it. To express it in numbers we need unit of light the lumen (lm). Thus we can say that the output of a 18W PLC tube downlight is 1250 lumens or that the recommended illuminance for a particular location is so many lumens per unit area.

Lux
               Illuminance is measured in lumens per square meter “lux”



Example for required Light Quantity
The store measuring 18.5m x 8.4m with 3.85 lamp height is to be provided with an illuminance consistence with good practice.
·        150 LUX requirement
·        Using 2 x 36W Mirror recessed light fitting (5400 lumens)
·        Assume reflectance of the ceiling is 0.5 and walls is 0.3

The first step is to calculate the flux received on the room.
               Flux received      = illuminance x area
                                             = 150 x (18.5 x 8.4)
                                             = 23,310 lumens

The flux which must be installed is such that when multiplied by utilization factor and by the light loss factor the resulting product is equal to the flux received.
               Flux installed x UF x LLF   = 23,310

In absence of special information it is normal to assume the light loss factor to be 0.75. To find the utilization factor we must first work out the room index
Room Index, k   =             LW        
                                                   Hm (L + W)
                                             =     18.5 x 8.4    
                                                  3.85 (18.5 + 8.4)
                                             = 1.5

Turning to the table utilization factor giving values for this type luminaire (Appendix I), for a room index 1.5 and ceiling and wall reflectances of 0.5 and 0.3 respectively we find that the UF is 0.38.
               Installed Flux      =        23,310      
                                                   0.38 x 0.75
                                             = 81,894.74 lumens

               Required quantity of light =    81,894.74 
                                                                     5,400
                                                               = 15.16 Nos.

               Thus the number of Light fitting needed is 16 Nos.
        
In practice, the fast calculation can do as follows:-
              
Quantity of Light Fitting =            Area x Lux          
                                                 Lumens x LLF x UF
                                                            =      (18.5 x 8.4) x 150     
                                                                5400 x 0.75 x 0.38
                                                            = 15.145

                                                            = 16 Nos.

AutoCAD-Plot Setup & Publish (Lesson Learn)

 Harini nak share sikit berkenaan AutoCAD. cara nak buat plot setup & publish. step ni amat penting sekiranya kita perlu print menggunak...