Requirements of Power System Protection
1. Fast: Fast operation in order to clear the fault from the system and minimize system damage.
2. Reliable: Work when required, and only when required. Protective equipment should not fail to operate in the events of fault in the protected zone.
3. Stable: To leave all healthy circuits intact and ensure continuity of supply.
4. Selective: Disconnection of equipment is restricted to the minimum necessary to isolate the fault.
5. Sensitive: Sensitive enough to operate under minimum fault condition.
Type of Protection
A. Unit Protection
1. Operates on differential principle, Kirchhoff’s current law
2. Discrimination by a defined ‘zone protection’ determined by CT
3. Must be stable during external fault
4. Fast operating time, typical:20-50ms
5. Main protection system
6. Example:
- Line/Transformer/Busbar differential, Restricted Earth Fault
- Defined by CT position


Non-Unit Protection: Overcurrent & Earth Fault protection
B. Non-Unit Protection
1. No defined area of coverage
2. Simple and cheaper
3. Slower operating time
4. Backup protection system
5. Discrimination by time factor
6. Requires time coordination between various stages
7. Example:
a. OCEF
-Time-delayed/IDMT: Can range from a few hundred milliseconds to several seconds,
-Depending on coordination with up/downstream devices.
b. SBEF (2000-5000ms)
Typical Protection Scheme for Cable
1. The cheapest protection relay compared to differential protection, REF etc.
2. Use standard characteristics:
a. Definite Time (DT)
b. Standard/ Normal Inverse (SI/NI)
c. Very Inverse (VI)
d. Extremely Inverse (EI)
e. Long Time Inverse (LTI)
Inverse Definite Minimum Time Characteristic (IDMT)
1. The relay operating time varies inversely with the magnitude of the fault current.
2. This means that the higher the fault current, the faster the relay will operate.
3. In contrast to definite-time relays, which have a fixed time delay, the operating time of inverse-time relays is dependent on the severity of the fault.
4. Normal Inverse characteristic
5. Normal Inverse calculation example
6. Calculation using website.
https://myelectrical.com/tools/idmt-tripping-time
7. IDMT Relay Operating Time
8. ANSI Device Function Numbers
Note refer from: Ir. Jamil Ahmad Radziyan (Warna RS Sdn Bhd)